Error Code 106

Cause:

  • Voltage and current signal incorrect
  • Impulse transformer incorrectly dimensioned

Measure during initial startup

  • Perform AUTOCAL.
  • Check transformer specifications.

Fault Area 7:

Explanation: UR signal incorrect

Possible cause: Secondary voltage U2 outside of permissible range of 0.4…120 VAC.

Fault Area 8:

Explanation: IR signal incorrect

Possible cause: Current I2 outside of permissible range of 30…500 A.

Fault Area 8:

Explanation: Turns incorrectly passed through current transformer

Possible cause: Check number of turns: Two or more turns required for currents < 30 A.

Measure during operation, HBAbbreviation HB not changed

Fault Area 4:

Explanation: Partial bypass (delta R)

Possible cause: Heating element partially bypassed by conducting part, e.g. clamp, opposite heat-sealing bar.

Fault Area 5:

Explanation: Parallel circuit interrupted

Possible cause:

  • Wire break, heating element break.
  • Contact to heating element is defective.

Fault Area 6:

Explanation: Total bypass

Possible cause:

  • Heating element incorrectly installed, no insulation at heat-sealing bar ends or insulation incorrectly installed.
  • Heating element completely bypassed by conducting part.

Fault Areas:

Request a callback

Use our callback service and provide your contact details. We will call you back as soon as possible.
*Mandatory field

Contact

ROPEX Industrie-Elektronik GmbH
Carl-Zeiss-Straße 20-22
D-74321 Bietigheim-Bissingen

Telephone: +49 7142 7776 0
Technical Support: +49 7142 7776 100
Inquiries / Orders: +49 7142 7776 250

Send e-mail