Part 3 of 3: Troubleshooting
Note
This section shows error messages that may occur if the AUTOCAL function is not ended properly.
The errors are initially reported as warnings.
- Analog output alternates between two values.
- ALARM LED flashes at 1 Hz.
- Alarm relay not active.
After the START signal is activated, the errors are reported as faults.
- Analog output no longer alternates; refer to bold value (e.g. 6.66).
- ALARM LED remains illuminated.
- Alarm relay is active.
Error code | Analog signal voltage [V]1) | Cause | Measure during initial startup | Measure during operation, HB2) not changed |
|---|---|---|---|---|
111 | 6.66/10 | Current signal incorrect, calibration not possible |
|
|
112 | 7.33/10 | Voltage signal incorrect, calibration not possible |
| |
113 | 8.00/10 | Voltage/current signal incorrect, calibration not possible |
| |
114 | 8.66/10 | Temperature fluctuates, calibration not possible |
| |
115 | External calibration temperature range too high, calibration not possible |
| ||
116 | External calibration temperature fluctuates, calibration not possible |
| ||
The voltage at the analog output alternates between the two values.
Heatsealing band