Part 2 of 3: Troubleshooting

The errors are initially reported as warnings.

After the START signal is activated, the errors are reported as faults.

Error code

Analog signal voltage [V]1)

Cause

Measure during initial startup

Measure during operation, HB2) not changed

104

5.33/10

  • Current signal incorrect
  • Impulse transformer incorrectly dimensioned
  1. Perform AUTOCAL.
  1. Check transformer specifications.
  1. Refer to fault areas 7 and 8.
  1. Refer to fault areas 4, 5 and 6 (loose contact).

105

  • Voltage signal incorrect
  • Impulse transformer incorrectly dimensioned

106

  • Voltage and current signal incorrect
  • Impulse transformer incorrectly dimensioned

302

  • Temperature too low
  • Calibration not performed
  • Loose contact
  • Ambient temperature fluctuates
  1. Perform AUTOCAL and/or refer to fault areas 4, 5, and 6 (loose contact).

303

  • Temperature too high
  • Calibration not performed
  • Loose contact
  • Ambient temperature fluctuates

211

6.00/10

Data error

  1. Perform AUTOCAL.
1)

The voltage at the analog output alternates between the two values.

2)

Heatsealing band