Part 1 of 3: Troubleshooting

The errors are reported as faults.

Error code

Analog signal voltage [V]

Cause

Measure during initial startup

Measure during operation, HB1) not changed

101

0.66

Current signal missing

  1. Fault area 1

102

1.33

Voltage signal missing

  1. Fault area 3

103

2.00

Voltage and current signals missing

  1. Fault area 2
  1. Fault area 2 and 9

107

2.66

Temperature drop

  1. Fault areas 4, 5 and 6 (loose contact)

108

Temperature spike

307

Temperature too low, tolerance band was left

  1. Check the dimensioning of the pulse transformer.
  1. Check heat extraction through the sealing process.
  1. Verify application through sealing tests.

308

Temperature too high, tolerance band was left

309

Temperature too low, tolerance band was not reached

310

Temperature too high, tolerance band was not reached

201

3.33

Line frequency missing/fluctuates

  1. Check mains power supply:
  • Line frequency
  • Harmonics
  • Voltage fluctuations

202

Line frequency too high/fluctuates

203

Line frequency too low/fluctuates

304

4.00

Heat-up time too long

  1. Reset device.
  1. Check dimensioning of the pulse transformer.
  1. Check parametrized heating time.
  1. Check lines and contacting.
  1. Reset device.
  1. Check lines and contacts.
  1. Check sealing process.

305

Starting temperature too high

  1. Reset device.
  1. Verify cooling system.
  1. Check maximum starting temperature.

901

4.66

Line voltage/synchronizing signal missing

  1. Check line voltage

913

Triac defective

  1. Replace device.

914

915

Internal error: Comparator in measuring module defective

916

Internal error: Test mode not ended successfully

917

918

Slide for alarm output not plausible.

  1. Check slide.

919

Internal error: Comparator in measuring mode not plausible

  1. Replace device.

920

  • Voltage signal not plausible
  • Internal error: Voltage change-over in measuring module defective
  1. Check heating circuits:
  • Check Relay Kb.
  • Check voltage signal.
  • Do not interrupt voltage signal during AUTOCAL.
  1. Reset device.
  1. Restart AUTOCAL.
  1. Replace device.

930

Internal communication module does not reply when temperature controller is switched on

  1. Switch device off and then on again.
  1. If the error code appears repeatedly, replace device.

931

Internal communication module indicates an error when temperature module is switched on

932

Internal communication module does not reply during operation

933

Internal communication module indicates an error during operation

934

Internal communication module does not reply during operation

935

Communication module firmware is not plausible (does not match device type)

  1. Replace device.

937

Internal communication module not started correctly

  1. Switch device off and then on again.
  1. If the error code appears repeatedly, replace device.

938

939

940

9412)

Internal error: Capacitor in measuring module defective

  1. Replace device.
1)

Heatsealing band

2)

Available beginning with firmware 313